Scope of work, 5%, 10%, 20%, 25%, more or less as per specifications and contracts signed.
HVAC (5 to 10% of Total)
SCOPE OF WORK GUIDE FOR SCHEMATIC DESIGN PHASE
1.            Prepare Outline Description including:
2.            Space requirements
3.            Sketches where required.
4.            Construction cost estimates in dollars per sq.
5.            Recommendations for studies and reports to be included in subsequent phases of work

Scope of work, 5%, 10%, 20%, 25%, more or less as per specifications and contracts signed. Continued.

HVAC (20-25% Total)
SCOPE OF WORK GUIDE FOR SCHEMATIC DESIGN PHASE
A.  General
B.  Scope of Work
1.  Update and confirm SDD Phase of work.
2.  Prepare Load estimates
a.            Using H-Load Program
b.            Use of hand Cal.
3.  Design criteria
4.  Energy analysis
5.  Drawings
a.            Abb. & sys. List
b.            Typical Fl. Plan
c.            Establishing space requirements and accessibility
d.           Establish weights of major equipment and average loads
e.            Typical AC system flow diagram
f.             Applicable flow and riser diagrams (air & Water).
6.  DD (Preliminary) Specification.
7.  Cost estimate
File: PPC. Memo. #25.0813, 2014
CC: PM of Each Trade

NYSEASIA.com; NYSEASIAWorld Worldwide, Philip Pai-Pin Chen

Date: Aug.13, 2014                 Memo. # 26            PPC/ADSC
Subject: ELECTRICAL/ SCOPE OF WORK GUIDE FOR SCHEMATIC DESIGN
Re:  HVAC/ M&E Design Input Data
Subject – HEAT LOSSES FOR TYPICAL ELECTRICAL EQUIPMENT
1.            TRANSFORMERS
A.                General – Approximate loss of 15KW per 1000 KVA.
B.                Dry Type, 600 volts and under : 30 thru 500 kva over
600 volts: 750 thru 1000 kva.
Approximate % Total loss
80Degree Temp Rise; 115 Degree Temp Rise; 150Degree Temp Rise; KVA Range
  2.58%              2.98%               4.20%          30 thru 75
  2.10%              2.30%               3.50%        112.5 thru 225
  1.45%              1.64%               2.30%        300 thru 500
  1.13%              1.32%               1.55%        750 thru 1000
l  Square D Company

C.                Oil Filled
Approximate % Total Loss
5/8.33 KV;       25KV class;        35 KV class;           KVA Range
5800 watts       6300 watts         6880 watts              500KVA
7500            8750              9400                   750
9900           10500             11500                  1000
14600          15400             16300                  1500
18500          19400             19900                  2000
22500          23900             24700                  2500

* W.H., Catalog 47-1x1 page 4, P. NETWORK

2.            UNIT SUBSTATIONS
A.            Transformers – Approximate loss of 15 kw per 1000 KVA
B.            Breakers (460v)- Approximate loss of 400w per breaker
C.            Breakers (4160v) – Approximate loss of 800w per breaker
l  Electrical Construction and Maintenance

3.  MOTOR CONTROL CENTER
A.            General – Approximate loss of 200w per vertical section
B.            Components
MOTOR CONTROL CENTER COMPONENTS
Component;     Size/Rating        Approximate Loss BTU per Minute
Magnetic         Size 1                 0.9
Starters          Size 2                 2.5
3                                                                        4.5
4                                                                        8.0
5                                                                        17.0
Circuit Breakers     100 Amps              0.5
                225 thru 600 amps          9.0

Fusible Switches     30 Amps               0.5
                   60 Amps               1.0
                  100 Amps               2.5
               200 thru 600 Amps           9.0
Control Transformers    50VA                0.5
                     100VA                0.9
                      150 VA               1.3
                       300VA               2.6
                       500VA               2.9
                       750VA                4.3
                       1000VA               5.7
* S. D. Company